Application |
---|
Application | Flow rate control, Temperature control, Wire break detection | < /tr>
Electronic data |
---|
Operating voltage tolerance [%] | -5…10 |
Rated AC voltage [V] | 90…240 |
Rated AC frequency [Hz] | 47…63 |
Protection class | II |
Reverse polarity protection | < td>no
Power-on delay time [s] | 10…80, (setting (fixed resistors terminals 22-23)) |
Number of channels | 1 |
Outputs |
---|
Characteristic in case of error | In the event of undervoltage, all relays are de-energized, the LED "Low power/relay connection is broken" light |
Electrical version< /td> | relay |
Contact load | 4 A (250 V AC / 30 V DC) |
Switching function flow rate monitoring | relay energised when flow is present and during the power-on delay time |
Switching function temperature monitoring | Relay de-energized in case of wire break or short circuit |
Relay de-energised in case of wire break or short circuit |
Short circuit protection | none |
Overcurrent protection | < td>none
Response time |
---|
Response time [s] | < 3 |
Software / Programming |
---|
Switch point setting | with potentiometer |
< tr>Preset selection for liquids/gases | wire bridge, device factory setting: liquid media monitoring, for gaseous media monitoring: connect terminals 23 / 24. | Threshold point setting | with potentiometer |
Temperature range [°C] | 0…80 |
Repeatability of set switch point [K] | 4 | < /tr>
Operating conditions |
---|
Ambient temperature [°C] | -20…60 |
Ambient temperature note | if there is enough free space for cooling under natural convection conditions | < /tbody>
|
Degree of protection | IP 20 |
Tests / approvals< /th> |
---|
MTTF [years] | 168 |
Mechanical data |
< tr>Weight [g] | 252.5 | Enclosure | Enclosure for DIN rail mounting |
Dimensions [mm] | 100 x 25 x 103.5 |
Material | PBT (polybutylene terephthalate) |
Displays / Controls |
---|
Display | Function | 11 x LED | Output status | LED, red st | Output status | LED, red |
|
Electrical connection |
---|
Required protection | miniature fuse IEC60127-2 sheet 1, ? 5 A, fast response |
Notes |
---|
Notes | Recommendations Check the safety of the device after a short circuit. |
|
Packing value | < td>1 piece
electrical connection |
---|
Connection | Combicon connector: |