Specifications ESM-BA701P 097225

If you are pursuing Euchner ESM-BA701P 097225, reach FAMAGA, the world's leading supplier of industrialized equipment. Our company has existed for more than ten years - these are ages of experience, which are expressed in the quality of products and particular attention to each client. We admire everyone, who cooperated with us - therefore, our regular purchasers receive the most acceptable purchase terms and discounts on the industrial equipment market. At present, there are more than 4500 such buyers, and we constantly arrange new agreements. More than 650 purchases are terminated per day, because FAMAGA supplies all over the earth . A well-shaped logistics system and a partnership network assist us to deliver our products anywhere in the world on-time without damaging product quality.

A particular source of honor for FAMAGA is its personnel, each of whom contributes to our work. We call into our team only experts, who already have experience in the direction of industrial equipment.

All products from FAMAGA are affirmed - we are responsible for the aftereffect of our work. At this moment, more than 10 million units of products have been shipped, and this number is amounting every day. We are glad that buyers choose FAMAGA again and again, and we are glad to make more advanced and technologically innovative industrial equipment so as keep on top of it.

To ask a question or place an order, call us by phone or write to the online chat on our site. You can also forward a list of the required equipment to the email of our company - we will contact you ourselves with a worked out commercial proposal from FAMAGA.

Features ESM-BA701P 097225

  • ESM-BA.. Usage up to category 4 according to EN ISO 13849-1
  • LED status indicators
  • 1-channel or 2-channel control
  • 7 redundant safety contacts
  • 4 auxiliary contacts
  • 2 monitoring contacts
  • Short circuit and earth fault/ground fault monitoring optional
  • Plug-in connection terminals
Relay outputsThe outputs are electrically decoupled and of redundant design. Connection optionsBy using suitable wiring the following functions can be selected:
  • Relay start with automatic start or a start button.
  • Monitoring of downstream relays or contactors
  • Simultaneity monitoring to monitor safety components over time.
  • Relay start using a monitored start button.
  • Short circuit monitoring to detect short circuits between the connection cables and to shut down the outputs or prevent relay starting if necessary.
  • Earth fault/ground fault monitoring to detect short circuits between the connection cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Auxiliary contactsThe relays in the series ESM?BA7 are available with electrically separate normally closed contacts and auxiliary contacts. Important:Two connection kits must be ordered for this device. Dimension drawing Wiring diagram Dimension drawingWiring diagram Technical dataApprovals Mechanical values and environment
Housing material Polyamide PA6.6
Weight
Net 0,35 kg
Ambient temperature -15 ... 40 °C
Degree of protection IP20
Mechanical life
operating cycles 10 x 106
Contact material AgSnO2
Mounting method Mounting rail 35mm according to DIN EN 60715 TH35
Number of monitoring outputs 2 semiconductor outputs
Connection Plug-in connection terminals
Length of control cable
With conductor cross-section 0.75mm2 1000 m
Monitoring outputs 01 / 02
Number of monitoring contacts 2
Auxiliary contacts 43/44, 53/54, 63/64, 73/74, 101/102, 101/112
Number of auxiliary contacts 4
Safety contacts 13/14, 23/24, 33/34, 81/82, 91/92
Number of safety contacts 7
Electrical connection ratings
Operating voltage
AC/DC 24 V -10% ... +10%
Power consumption (apparent power)
At 24V AC 8,5 VA
Rated insulation voltage Ui 250 V
Rated impulse withstand voltage Uimp
Leakage path/air gaps 4 kV
Overvoltage category according to IEC EN 60664-1 3
Reverse polarity protection
On version UB=24V DC
Degree of contamination (external, according to EN 60947-1) 2
Connecting cable
at 24V DC 4,5
Connection cross-section 0,14 ... 2,5 mm? Connection terminal (size)
Test voltage
Control system/contacts 2,5 kV
Control voltage
On S11 24 V 18,6 ... 26 V Start button
Control current
S11...S14 250 mA
LED indicator 1 status displays operating voltage (Pwr), 2 status displays (green) for relays K1 and K2
Monitoring outputs 01 / 02
Type of output
Semiconductor output PNP Short circuit-proof
Output voltage 24 V DC
Output current max.30 mA
Auxiliary contacts 43/44, 53/54, 63/64, 73/74, 101/102, 101/112
Type of output
NO contact / NC contact Relay contacts, floating
Utilization category according to EN 60947-5-1
AC-15 3A, 250V
DC-13 3A, 24V
AC-12 8A, 250V
DC-12 8A ohmic load, 50V
Breaking capacity according to UL
Auxiliary contact 2A 250V AC / 1.5A 24V DC
Safety contacts 13/14, 23/24, 33/34, 81/82, 91/92
Type of output
NO contact / NC contact Relay contacts, floating and positively driven (redundant)
Switching voltage
AC max.250 V
DC max.50 V
Switching current min.5 mA at 24V
Cumulative current max.35 A For all contacts
Fusing
External contact fuses (safety circuit) according to IEC 60269-1 10AgG (T6A / F8A)
Utilization category according to EN 60947-5-1
AC-15 3A, 250V
DC-13 3A, 24V
AC-12 8A ohmic load, 250V
DC-12 8A ohmic load, 50V
Breaking capacity according to UL
Safety contacts 8A 250V AC / 2A 24V DC per contact
Other
In compliance with EN 60439-1:1999+A1:2004 , EN 60947-1:2007 , EN 60947-5-1:2004 , EN 60947-7-1:2002 , EN 61000-6-2:2005 , EN 61000-6-3:2007 , EN ISO 13849-1:2008 , EN 62061:2005 , EN 60204-1:2007
Reliability values according to EN ISO 13849-1
Performance Level PL e
Category 4
PFHD 2.47 x 10-8
Number of switching cycles
? 0.1 A at 24 V DC max.500000 1/Jahr
? 2 A at 24 V DC max.100000 1/Jahr
? 1 A at 24 V DC max.350000 1/Jahr
Mission time 20 y